home *** CD-ROM | disk | FTP | other *** search
/ PC World Komputer 1996 September / PCWK996.iso / polskie / enpro / sieci / wsi.dat < prev    next >
Text File  |  1996-04-16  |  7KB  |  134 lines

  1. .
  2.       WSPú£CZYNNIKI POPRAWKOWE PRZY U£OíENIU RúWNOLEG£YM KABLI
  3.       UMIESZCZONYCH W POWIETRZU O TEMPERATURZE OBLICZ. + 25 st.C
  4. .
  5. .     ===================================================================
  6. .                                Kable uÆoºone w odlegÆo₧ciach
  7.                     Liczba       od ₧ciany - 2 cm i wiæcej
  8.       UÆoºenie      warstw       miædzy sobå - równej ₧rednicy kabla
  9.       kabli         uÆoºon.     ---------liczba kabli w warstwie---------
  10.                     kabli        1         2        3        6       9
  11.       -------------------------------------------------------------------
  12.       w korytach      1         0.95      0.90     0.88     0.85    0.84
  13.       (utrudniona     2         0.90      0.85     0.83     0.81    0.80
  14.        cyrkulacja     3         0.88      0.83     0.81     0.79    0.78
  15.        powietrza)     6         0.86      0.81     0.79     0.77    0.76
  16.       -------------------------------------------------------------------
  17.          na           1         1.00      0.98     0.96     0.93    0.92
  18.       wspornikach     2         1.00      0.95     0.93     0.90    0.89
  19.                       3         1.00      0.94     0.92     0.89    0.83
  20.                       6         1.00      0.93     0.90     0.87    0.86
  21.       -------------------------------------------------------------------
  22.       kable uÆoºone
  23.       na podÆodze     1         0.95      0.90     0.88     0.85    0.84
  24.       -------------------------------------------------------------------
  25.       kable uÆoºone
  26.       na wspornikach  -         1.00      0.93     0.90     0.87    0.86
  27.       nad sobå
  28.       ===================================================================
  29. .
  30. .   
  31. .
  32. .     ===================================================================
  33. .                                Kable stykajå siæ ze ₧cianå
  34.                     Liczba               i miædzy sobå
  35.       UÆoºenie      warstw       
  36.       kabli         uÆoºon.     ---------liczba kabli w warstwie---------
  37.                     kabli        1         2        3        6       9
  38.       -------------------------------------------------------------------
  39.       w korytach      1         0.95      0.84     0.80     0.75    0.73
  40.       (utrudniona     2         0.95      0.80     0.75     0.71    0.69
  41.        cyrkulacja     3         0.95      0.78     0.74     0.70    0.68
  42.        powietrza)     6         0.95      0.76     0.72     0.68    0.66
  43.       -------------------------------------------------------------------
  44.          na           1         0.95      0.84     0.80     0.75    0.73
  45.       wspornikach     2         0.95      0.80     0.76     0.71    0.69
  46.                       3         0.95      0.78     0.74     0.70    0.68
  47.                       6         0.95      0.76     0.72     0.68    0.66
  48.       -------------------------------------------------------------------
  49.       kable uÆoºone
  50.       na podÆodze     1         0.90      0.84     0.80     0.75    0.73
  51.       -------------------------------------------------------------------
  52.       kable uÆoºone
  53.       bezpo₧rednio    -         0.95      0.78     0.73     0.68    0.66
  54.       na ₧cianie
  55.       ===================================================================
  56. .
  57. .
  58. *************************************************************************
  59. .
  60.     WSPú£CZYNNIKI POPRAWKOWE OBOWIÅZUJÅCE PRZY TEMPERATURZE OBLICZ.
  61.     OTOCZENIA WYíSZEJ od + 25 st. C.
  62. .
  63. .    ===================================================================
  64.                          Dopuszczalna temp. graniczna przewodu  
  65.       Oblicz. temp.             lub kabla w st. C 
  66.       otoczenia       --------------------------------------------------
  67.       w st. C         45     50     60     65    70     80    85    105
  68.       ------------------------------------------------------------------
  69.          30           0.87   0.89   0.92   0.93  0.94   1.00  1.00  1.00
  70.          35           0.71   0.78   0.84   0.86  0.88   1.00  1.00  1.00
  71.          40           0.50   0.63   0.75   0.79  0.81   0.94  1.00  1.00
  72. .
  73.          45            -     0.45   0.69   0.70  0.74   0.88  0.94  1.00
  74.          50            -      -     0.53   0.61  0.66   0.81  0.88  1.00
  75.          55            -      -     0.37   0.50  0.57   0.74  0.81  1.00
  76. .
  77.          60            -      -      -     0.35  0.47   0.66  0.74  1.00
  78.          65            -      -      -      -    0.33   0.57  0.66  0.94
  79.          70            -      -      -      -     -     0.47  0.57  0.88
  80. .
  81.          75            -      -      -      -     -     0.33  0.47  0.81
  82.          80            -      -      -      -     -      -    0.33  0.74
  83.          85            -      -      -      -     -      -     -    0.66
  84. .
  85.          75            -      -      -      -     -      -     -    0.57
  86.          80            -      -      -      -     -      -     -    0.47
  87.          85            -      -      -      -     -      -     -    0.33
  88.      ====================================================================
  89. .
  90. .
  91. *************************************************************************
  92. .
  93.     WSPú£CZYNNIKI POPRAWKOWE PRZY RúWNOLEG£YM U£OíENIU KABLI
  94.     W KANA£ACH NA DNIE, BEZ SZTUCZNEJ WENTYLACJI.
  95. .
  96.       ===============================================
  97. .        Liczba kabli               WspóÆczynnik
  98.          uÆoºonych równol.          poprawkowy
  99.       -----------------------------------------------
  100.                2                       0.87
  101.              3 i 4                     0.80
  102.              5 i wiæcej                0.72
  103. .     ===============================================
  104. .
  105. .
  106. ************************************************************************
  107. .
  108. .
  109.     WSPú£CZYNNIKI POPRAWKOWE DLA IZOLOWANYCH PRZEWODúW WIELOíY£OWYCH
  110.     LUB KABLI U£OíONYCH POJEDYÑCZO W RURACH WYKONANYCH Z DOWOLNEGO
  111.     MATERIA£U LUB W PRZEPUSTACH KABLOWYCH UMIESZCZONYCH W POWIETRZU
  112.     O TEMP. OBLICZ. + 25 stopni C.
  113. .
  114. .     ==========================================================
  115.         Rodzaj przewodu lub kabla            WspóÆczynnik popr.
  116.       ----------------------------------------------------------
  117.         Przewody wieloºyÆowe o 
  118.         przekroju ºyÆ do 120 mm2                  0.90
  119.         wÆåcznie
  120.       ----------------------------------------------------------
  121.         Przewody wieloºyÆowe o
  122.         przekroju ºyÆ 150 mm2                     0.85
  123.       ----------------------------------------------------------
  124.         Kable na napiæcie do 10 kV
  125.         wÆåcznie o dowolnym prze-                 0.74
  126.         kroju ºyÆ
  127.       ==========================================================
  128. .
  129. .
  130. .
  131. ---------------------------koniec--------------------------------------