WSPú£CZYNNIKI POPRAWKOWE PRZY U£OíENIU RúWNOLEG£YM KABLI
UMIESZCZONYCH W POWIETRZU O TEMPERATURZE OBLICZ. + 25 st.C
.
. ===================================================================
. Kable uÆoºone w odlegÆo₧ciach
Liczba od ₧ciany - 2 cm i wiæcej
UÆoºenie warstw miædzy sobå - równej ₧rednicy kabla
kabli uÆoºon. ---------liczba kabli w warstwie---------
kabli 1 2 3 6 9
-------------------------------------------------------------------
w korytach 1 0.95 0.90 0.88 0.85 0.84
(utrudniona 2 0.90 0.85 0.83 0.81 0.80
cyrkulacja 3 0.88 0.83 0.81 0.79 0.78
powietrza) 6 0.86 0.81 0.79 0.77 0.76
-------------------------------------------------------------------
na 1 1.00 0.98 0.96 0.93 0.92
wspornikach 2 1.00 0.95 0.93 0.90 0.89
3 1.00 0.94 0.92 0.89 0.83
6 1.00 0.93 0.90 0.87 0.86
-------------------------------------------------------------------
kable uÆoºone
na podÆodze 1 0.95 0.90 0.88 0.85 0.84
-------------------------------------------------------------------
kable uÆoºone
na wspornikach - 1.00 0.93 0.90 0.87 0.86
nad sobå
===================================================================
.
.
.
. ===================================================================
. Kable stykajå siæ ze ₧cianå
Liczba i miædzy sobå
UÆoºenie warstw
kabli uÆoºon. ---------liczba kabli w warstwie---------
kabli 1 2 3 6 9
-------------------------------------------------------------------
w korytach 1 0.95 0.84 0.80 0.75 0.73
(utrudniona 2 0.95 0.80 0.75 0.71 0.69
cyrkulacja 3 0.95 0.78 0.74 0.70 0.68
powietrza) 6 0.95 0.76 0.72 0.68 0.66
-------------------------------------------------------------------
na 1 0.95 0.84 0.80 0.75 0.73
wspornikach 2 0.95 0.80 0.76 0.71 0.69
3 0.95 0.78 0.74 0.70 0.68
6 0.95 0.76 0.72 0.68 0.66
-------------------------------------------------------------------
kable uÆoºone
na podÆodze 1 0.90 0.84 0.80 0.75 0.73
-------------------------------------------------------------------
kable uÆoºone
bezpo₧rednio - 0.95 0.78 0.73 0.68 0.66
na ₧cianie
===================================================================
.
.
*************************************************************************
.
WSPú£CZYNNIKI POPRAWKOWE OBOWIÅZUJÅCE PRZY TEMPERATURZE OBLICZ.
OTOCZENIA WYíSZEJ od + 25 st. C.
.
. ===================================================================
Dopuszczalna temp. graniczna przewodu
Oblicz. temp. lub kabla w st. C
otoczenia --------------------------------------------------
w st. C 45 50 60 65 70 80 85 105
------------------------------------------------------------------
30 0.87 0.89 0.92 0.93 0.94 1.00 1.00 1.00
35 0.71 0.78 0.84 0.86 0.88 1.00 1.00 1.00
40 0.50 0.63 0.75 0.79 0.81 0.94 1.00 1.00
.
45 - 0.45 0.69 0.70 0.74 0.88 0.94 1.00
50 - - 0.53 0.61 0.66 0.81 0.88 1.00
55 - - 0.37 0.50 0.57 0.74 0.81 1.00
.
60 - - - 0.35 0.47 0.66 0.74 1.00
65 - - - - 0.33 0.57 0.66 0.94
70 - - - - - 0.47 0.57 0.88
.
75 - - - - - 0.33 0.47 0.81
80 - - - - - - 0.33 0.74
85 - - - - - - - 0.66
.
75 - - - - - - - 0.57
80 - - - - - - - 0.47
85 - - - - - - - 0.33
====================================================================
.
.
*************************************************************************
.
WSPú£CZYNNIKI POPRAWKOWE PRZY RúWNOLEG£YM U£OíENIU KABLI
W KANA£ACH NA DNIE, BEZ SZTUCZNEJ WENTYLACJI.
.
===============================================
. Liczba kabli WspóÆczynnik
uÆoºonych równol. poprawkowy
-----------------------------------------------
2 0.87
3 i 4 0.80
5 i wiæcej 0.72
. ===============================================
.
.
************************************************************************
.
.
WSPú£CZYNNIKI POPRAWKOWE DLA IZOLOWANYCH PRZEWODúW WIELOíY£OWYCH
LUB KABLI U£OíONYCH POJEDYÑCZO W RURACH WYKONANYCH Z DOWOLNEGO
MATERIA£U LUB W PRZEPUSTACH KABLOWYCH UMIESZCZONYCH W POWIETRZU
O TEMP. OBLICZ. + 25 stopni C.
.
. ==========================================================
Rodzaj przewodu lub kabla WspóÆczynnik popr.
----------------------------------------------------------
Przewody wieloºyÆowe o
przekroju ºyÆ do 120 mm2 0.90
wÆåcznie
----------------------------------------------------------
Przewody wieloºyÆowe o
przekroju ºyÆ 150 mm2 0.85
----------------------------------------------------------
Kable na napiæcie do 10 kV
wÆåcznie o dowolnym prze- 0.74
kroju ºyÆ
==========================================================
.
.
.
---------------------------koniec--------------------------------------
.
.
.